HECM INPUT OUTPUT MODULE
- 19”, 1U rack type compact design
- 54 pcs Channels Led Technology
- Customized Input/Output Quantity & Current Rating; Flexible Structure
- Voltage supervised Outputs
- Internal Event Memory
- Standard Communication and Event Recording Feature
- Reliable Performance Under Electromagnetic Interference
- Working under Different Voltage Levels. (24/48and 110/220 Vdc)
- Isolated RS485 Port and ModbusRTU Protocol Support
- IEC61850 Protocol Support (optional)
- Irig-B Time synchronization with Irig-b Optional card
- High-quality and long life power supply with protection for over temperature, short circuit, overcurrent/overvoltage
HECM Modular Input/Output is a flexible, functional and reliable product used in the protection and control automation systems
Our product, combining low cost with good quality, compact and unique design, is an unrivaled product with standard communication and event recording features.
It has electronic card alternatives for different applications. With the help of 3pcs modular slots inside the unit, it has a flexible structure which quantities of inputs/outputs, current ratings are decided upon customer requirements. Each input is isolated. It is protected by opto-coupler, harmonic suppressors and noise filtering software. The device can be safely used under the environment containing high electromagnetic noise which is continuously met. Outputs could be relay or solidstate type.
Having event recording features with 1 msec resolution and 2.000 event memory.
Response and release time for the environment with electromagnetic noise are to be programmed between 3-250msec.
RS485 communication port supports Modbus RTU and could be easily integrated with the SCADA systems. By installing IRIG-B Optional card, you can time synchronize it with Irig-B format.
By utilizing IEC61850 Protocol Management Card (PMC) option, it can be used as a I/O module which is capable of connecting to the IEC61850 compatible systems .
It can be used as I/O module of our HEEP3000 event recorder product
PHOTO GALLERY
GENERAL FEATURES
19” RACK TYPE MODULAR CONSTRUCTION
HECM Modular Input/Output, having 1U 19” physical structure, provides flexible, smart, functional and reliable solutions for protection and control automation.It could be easily used in the wide area protection systems, thanks to the parallel working feature on a RS485 bus.
COMMUNICATION
The integrated RS485 serial communication port with galvanic isolation protection, supports Modbus RTU protocol and get easily adapted to the SCADA systems. Via optional IEC61850 Protocol Management Card, it can connect to the IEC61850 compatible systems.
INTERNAL EVENT RECORDER
It is an ideal device for wide area protection systems with sequential event recording in 1ms resolution timestamps, enhanced storage(2.000 event buffer) and software supported reporting features. Additionaly by installing optional IRIG-B card, you can time synchronize it with Irig-B format.
LED INDICATION
It has energy saving LED indication, providing high quality illumination. It provides isolated independent LED for each channel status and supervision and ultra bright illumination which could be seen even in the high lighting environments.
FULL SOFTWARE CONFIGURATION
With the help of ISPsim™ software; just one response and release time valid for all channels as well as ModbusID setting can be programmed. Additionally, all I/O channels could be tested in simulator screen and all of time stamped events could be viewed. ISPsim™ software can be downloaded from here
INPUTS AND OUTPUTS
All inputs are isolated with opto-coupler, protected with varistor, having common return terminal and filtered. Fulfill EU Electromagnetic Compatibility (EMC) and Low voltage directive (LVD). False alarm possibility is completely eliminated. The maximum input current is 5mA, the input voltage can be ordered as 24/48V,110/220Vdc upon request.
Outputs could be relay or solidstate type upon switching current requirements. Outputs are voltage supervision type, so that supervision LED corresponding this channel will indicate the situation, in case of any fault or wiring break in the channel.
INPUT AND OUTPUTS ALTERNATIVES
Input card alternatives for each slot ;
- 16 channels input card, 110/220Vdc
- 16 channels input card, 24/48Vdc
Output card alternatives for each slot;
- 8 channels, relay outputs card, breaking rating of [email protected]/ 0,[email protected],
- 8 channels, relay outputs card, breaking rating of [email protected]/ 0,[email protected],
- 4 channels, solidstate outputs card, breaking rating of [email protected]
PROGRAMMABLE RESPONSE AND RELEASE TIME
There are “software programmable” response – release times which provide flexible and safe performance for protection against induced magnetic fields resulted from maneuvers i.e CB opening/closing especially. With the help of ISPsimTM software; Response and release time valid for all channel are set between 3msec and 250msec. Response time is set to 5msec, release time is set to 20msec by default.
HIGH-QUALITY POWER SUPPLY
HECM modular Input/Output, can be supplied with 2 different voltage level in order to meet the different alternatives used in the distribution system automation. It can be freely connected to the voltage levels of 24/48V, 110/220Vdc. Power supply with the design of protection against shortcircuit, overcurrent/overvoltage and over temperature, guarantees long life
CASE AND MOUNTING
HECM is provided in 1U, 19” Rack type case configuration. Having Standard dimensions of (340x45x192mm), with user-friendly rack mounting system, it can be fast and safely mounted / dismantled.
EASY TO USE
Inputs of HECM are activated by connecting contacts outputs of protection relay on the field to the device. Whenever signal occurs at the input, LED Corresponding input indicates its channel status. Outputs are decided according to the ratings of the load to be switched. It is understood that relay dry contact is activated, by seeing that corresponding LED is ON. Additionaly it is understood that the wiring or the connected device is faulty, by checking voltage supervision LED.
Wiring and other details are provided in the instruction manual of the device.
APPLICATION ALTERNATIVES
HECM,
- As I/O module of our HEEP3000 event recorder product.
- By installing IRIG-B optional card, you can time synchronize it with Irig-B format.
- By utilising IEC61850 Protocol Management Card (PMC) option, it can be used as a I/O module which is capable of connecting to the IEC61850 compatible systems.
INNOVATIVE ASPECTS
Innovative aspects of HECM are as follows:
- Input and output functions are combined in the same case.
- The quantity of inputs and outputs could be decided upon request.
- The risks of unnecessary maneuvers are decreased by internal fault control utilizing voltage supervision.
- It enables operational safety, economic savings by terminating protection relay contact wiring (of 110/220Vdc) in the substation.
- By supporting IEC61850, it can easily communicate with IEDs in the field and with SCADA in the control room.
ORDER CODES
HECM TYPE CODE |
Input |
Output |
HEIM-48I-DC110/220 |
48 |
|
HEOM-24O-DC110/220-5A (ops 8A) |
24 |
|
HECM-16I16O-DC110/220-5A (ops 8A) |
16 |
16 |
HECM-32I8O-DC110/220-5A (ops 8A) |
32 |
8 |
HECM-32I4O-DC110/220-8Adc |
32 |
4 |
DOCUMENTS
TECHNICAL FEATURES
HECM |
24/48Vdc |
110/220Vdc |
||
Suplly |
||||
Supply Voltage range |
18...72Vdc |
88...242Vdc |
||
Supply power |
10w |
|||
Input Card |
||||
Qty of Inputs |
16 |
|||
Type of Inputs |
Optical Isolated, Varistor Protected, Common return terminal,transient filtered |
|||
Input Curr. (Per channel) |
Max. 5 mA |
Max. 5 mA |
||
Input Impedance (min) |
15kΩ |
85 kΩ |
||
Input threshold voltage |
12V ±20% |
65 V ± 20% |
||
Transient Voltage |
Common Mode: 1kV – Serial Mode: 2kV |
|||
Response time |
Programmable 3...250msec, Default : 5 msec |
|||
Release time |
Programmable 3...250msec, Default : 20 msec |
|||
Connection type |
Screwed, pluggable type terminals |
|||
Wire size |
12 AWG (2.5 mm) |
|||
Output Card |
||||
Type of Output Card |
Relay 8A |
Relay 5A |
SolidState |
|
Qty & Type of Outputs |
8pcs NO dry contact |
8pcs NO dry contact |
4pcs SolidState |
|
Qty. of LED for sup.input |
8pcs of LEDs for supervised channels |
8pcs of LEDs for supervised channels |
4pcs of LEDs for supervised channels |
|
Contact breaking current |
[email protected], 0,[email protected],L/R=40ms |
[email protected], 0,[email protected],L/R=40ms |
[email protected],L/R=40ms |
|
Communication |
||||
Comm. Port/Protocol |
RS485 / Modbus RTU (19200/8/n/1); For Scada connection, by default |
|||
Comm. Port/Proto. (ops) |
RS485; optional for IRIG-B time server |
|||
Comm. Port/Proto. (ops) |
RJ45 ethernet; optional for IEC61850 connection |
|||
Event Recorder |
||||
Event Recorder |
Yes for Input Channels |
|||
HECM-RTU Integration |
Yes for Input Channels |
|||
User Interface |
||||
LED indication |
48 pcs of LEDs for channels & Supervision/ 4 pcs of LEDs for 2pcs Comm./ 1pcs LED for CONFIG / 1pcs LED for PowerSupply |
|||
Case |
||||
Case type |
1U, 19” Rack type |
|||
Dimensions(WxHXD) |
340x45x192mm (dimensions of L shaped part for side mounting;20x45x56mm, thickness;2.2mm) |
|||
PanelMounting |
Rack mounting type |
|||
Protection Class |
IP20 |
|||
Weight |
Depens up on card configuration in the slots |
|||
Environmental Features |
||||
Operating temperature |
-20 C ... +50 oC |
|||
Storage temperature |
-25 C ... +80 oC |
|||
Humidity |
0-95% RH |
|||
Package |
||||
Package type |
Carton Box |
|||
Package dimensions(WxHxD) |
496x83x245mm |
|||
Weight |
Depens up on card configuration in the slots |